HVDC地中直流对交流系统的影响及规律分析
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
直流输电系统在系统调试或故障情况下会处于单极大地回路运行方式,这时地中直流会对交流系统的正常运行带来不利影响。为此全面总结了我国龙政、天广、三广直流输电线路在调试与运行过程中对附近交流电网运行带来的噪声、谐波、振动等不利影响;通过贵广调试现场实验及对实测数据的详细分析,归纳得到变压器中性点直流、谐波、噪声等与入地直流之间的关系规律;通过建立理论模型,对于地中直流的分布特性进行了分析,并以春城变电站为例就中性点直流电流进行了计算。计算结果验证了所提理论模型和计算方法的有效性。
The HVDC transmission system may be operated in ground return mode when the system is in debug or failure. The disadvantages, such as audible noise, harmonic and oscillation of the transformer in AC systems, are illustrated by analyzing the data of LONG-ZHENG, TIAN-GUANG and SAN-GUANG HVDC system. And field experiments were implemented by measuring the neutral DC current of more than ten transformers when the GUI-GUANG HVDC system was in debugging. Some useful data were acquired and some interesting results were obtained by analyzing these data. Based on the field-circuit theory model, the DC ground current flowing through the neutral point of the transformer was analyzed, and the result verified the feasibility of the theoretical model.
引文
[1]刘海峰,徐政,金丽成.世界远距离大容量高压直流输电工程可靠性调查综述[J].高压电器,2002,38(3):1-4,6.LI U Hai-feng,XU Zheng,JI N Li-cheng.Areviewof the relia-bility survey of long distance high power HVDC transmission project throughout the world[J].High Voltage Apparatus,2002,38(3):1-4,6.
    [2]宁凤辉,赵中原,邱毓昌.三峡至常州±500kV高压直流输电用晶闸管技术特点[J].高压电器,2003,39(4):62-63,69.NI NG Feng-hui,ZHAO Zhong-yuan,QI U Yu-chang.Tech-nique features of thyristor valve used for±500kV HVDC transmission from the Three Gorges to Changzhou[J].High Voltage Apparatus,2003,39(4):62-63,69.
    [3]赵畹君.高压直流输电工程技术[M].北京:中国电力出版社,2004.
    [4]赵杰,曾嵘,黎小林,等.HVDC输电系统地中直流对交流系统的影响及防范措施研究[J].高压电器,2005,41(5):324-326,329.ZHAOJie,ZENG Rong,LI Xiao-lin,et al.Study onthei mpact of HVDC ground return current on AC system and resolutions[J].High Voltage Apparatus,2005,41(5):324-326,329.
    [5]韩晓东,翟亚东.高压直流输电用换流变压器[J].高压电器,2002,38(3):5-6.HAN Xiao-dong,ZHAI Ya-dong.Converter transformer used for HVDCtransmission[J].High Voltage Apparatus,2002,38(3):5-6.
    [6]盛宝良,Hans-Ola Bjarme,Saksvik O,等.现代高压直流输电技术及直流阀技术[J].高压电器,2003,39(6):47-50.SHENG Bao-liang,Hans-Ola Bjarme,Saksvik O,et al.Mod-ern HVDC thyristor valves and HVDC transmission technolo-gies[J].High Voltage Apparatus,2003,39(6):47-50.
    [7]蔡希鹏.500kV天广直流输电系统交流滤波器频繁投切分析[J].电网技术,2005,29(4):1-3.CAI Xi-peng.Analysis on frequent switching of AC filter in Tian-Guang HVDC project[J].Power System Technology,2005,29(4):1-3.
    [8]毛晓明,吴小辰.南方交直流并联电网运行问题分析[J].电网技术,2004,28(2):6-19.MAO Xiao-ming,WU Xiao-chen.Analysis on operational prob-lems in south CHI NA AC-DC hybrid power grid[J].Power Sys-tem Technology,2004,28(2):6-19.
    [9]王明新,张强.直流输电系统接地极电流对交流电网的影响分析[J].电网技术,2005,29(3):9-14.WANG Ming-xin,ZHANG Qiang.Analysis on influence of ground electrode current in HVDC on AC power network[J].Power System Technology,2005,29(3):9-14.
    [10]钟连宏,陆培均,仇志成,等.直流接地极电流对中性点直接接地变压器影响[J].高电压技术,2003,29(8):12-13.ZHONG Lian-hong,LUPei-jun,QIUZhi-cheng,et al.Theinflu-ence of current of DCearthing electrode on directly groundedtrans-former[J].High Voltage Engineering,2003,29(8):12-13.
    [11]GB/T14549-1993电能质量:公用电网谐波[S],1993.GB/T14549-1993Quality of electric energy supply:harmon-ics in public network[S],1993.
    [12]广东省电力试验研究所.贵广直流极2系统单极大地回线方式对广东电网变压器影响的测试报告[R].广州:广东省电力试验研究所,2004.
    [13]南方电网技术研究中心.HVDC系统地中电流对交流系统及其它设施的影响及防范措施研究[R].广州:南方电网技术研究中心,2005.
    [14]张波,崔翔,赵志斌,等.大型变电站接地网的频域分析方法[J].中国电机工程学报,2002,22(9):59-63.ZHANG Bo,CUI Xiang,ZHAO Zhi-bin,et al.Analysis of grounding grids at large scale substations in frequency domain[J].Proceedings of the CSEE,2002,22(9):59-63.
    [15]滕吉文.固体地球物理学概论[M].北京:地震出版社,2003.
    [16]Kappenman J G,Norr S R,Sweezy G A,et al.GIC mitiga-tion:a neutral blocking/bypass device to prevent the flow of GICin power systems[J].IEEE Transactions on Power Deliv-erZyE,N19G91R,on6g(3):1271-1281.

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心