CFRP加固现浇框架结构节点柱端的强柱弱梁效果
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
对现浇钢筋混凝土框架结构节点梁端与柱端抗弯承载力进行了分析计算,考虑了现浇楼板内钢筋对梁抗弯承载力的影响,对现浇框架结构普通梁柱节点和在柱端外包碳纤维的节点的计算结果进行对比分析。结果表明,现浇楼板内的钢筋参与了梁的工作,提高了梁的抗弯承载力。柱端外包碳纤维后柱端承载力得到了明显的提高,推迟了柱端塑性铰的出现,更加接近总体机制破坏。
The calculation for flexural capacity of beam end and column end were carried out,with the strength effect of slab bar being included.The results for traditional joint specified in design code and that for the joint retrofitted with hybridized CFRP were compared.The results presented the efficiency of flexural strength improvement in beam.It is also shown that for the joint retrofitted with hybridized CFRP,the stress in the reinforce bar for column will increase significantly,while the plastic pivot of column appears later,which tend to exhibit a failure type closer to the beam-pivot or ductile mode.
引文
[1]李宏男,肖诗云,霍林生.汶川地震震害调查与启示[J].建筑结构学报,2008,29(4):10-19.
    [2]赵彤,谢剑.碳纤维布补强加固混凝土结构新技术[M].天津:天津大学出版社,2001.
    [3]陆洲导,宋彦涛,王李果.碳纤维加固混凝土框架节点的抗震试验研究[J].结构工程师,2004,20(5):39-43.
    [4]余琼.框架节点加固方法探讨[J].结构工程师,2004,1(1):62-70.
    [5]黄小奎,崔凯成,熊丹安.碳纤维布加固梁柱节点试验研究[J].武汉理工大学学报,2004,26(2):30-33.
    [6]王步,王溥,夏春红.核芯区外碳纤维布增强混凝土框架节点抗剪性能试验研究与机理分析[J].工业建筑,2005,35(7):29-33.
    [7]吴波,王维俊.碳纤维布加固钢筋混凝土框架节点的抗震性能试验研究[J].土木工程学报,2005,38(4):60-65.
    [8]谢剑,刘明学,赵彤.碳纤维布提高高强混凝土柱抗震能力评估方法[J].天津大学学报,2005,38(2):109-113.