1000kV输电铁塔抗震设计及振动台试验研究
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
为研究特高压输电塔的抗震性能,以1 000 kV"皖电东送"淮南—上海输变电工程同塔双回路SZ272P钢管塔和晋东南—南阳—荆门输电线路酒杯型ZBS1角钢直线塔为原型,依据相似理论进行分析,设计并制作缩尺振动台试验模型,分别进行单塔、单塔挂质量块和塔线耦联体系地震模拟振动台试验,验证了1 000 kV钢管和角钢模型塔在8度罕遇地震作用下的抗震性能,提出了抗震设计改进建议。
In order to study the seismic performance of UHV transmission tower,taking the SZ272P steel tube tower in double-circuit 1 000 kV Huainan-Shanghai transmission line and the ZBS1 cup-type angle line tower in Jindongnan-Jingmeng transmission as project background,this paper designed and made the scale model of shaking table test,based on the similarity theory. Three cases of the models,single tower,tower with concentrated mass to simulate the conductors and tower-conductor coupled system,were tested on the shaking table,whose results verified the seismic performance of the 1 000 kV steel tube tower and the angle tower in the rare earthquake of 8 degree. Finally,some suggestions for seismic design were proposed.
引文
[1]Xie Q,Zhu R.Earth,wind,and ice[J].Power and Energy Magazine,2011,9(2):28-36.
    [2]谢强,白杰,薛松涛,等.1 000 kV特高压角钢塔地震模拟振动台实验研究[J].电网技术,2013,37(1):58-64.
    [3]谢强,白杰,薛松涛,等.特高压输电线路塔线耦联体系非线性振动响应振动台试验研究[J].地震工程与工程振动,2012,32(5):103-110.
    [4]谢强,白杰,薛松涛.特高压交流同塔双回输电塔地震模拟振动台试验[J].高电压技术,2012,38(6):1410-1419.
    [5]GB 50665—2011 1 000 kV架空输电线路设计技术规范[S].北京:中国计划出版社,2011.
    [6]GB 50011—2010建筑抗震设计规范[S].北京:中国建筑工业出版社,2010.
    [7]DL/T 5154—2002架空送电线路杆塔结构设计技术规定[S].北京:中国电力出版社,2002.
    [8]沈国辉,孙炳楠,何运祥,等.大跨越输电塔线体系的地震响应研究[J].工程力学,2008,25(11):212-217.
    [9]曹枚根,周福霖,徐忠根,等.大跨越输电塔线体系减震控制分析研究[J].电网技术,2007,31(14):45-51.
    [10]韩大刚,黄兴,肖兵,等."皖电东送"工程特高压钢管塔设计总结及建议[J].电力建设,2013,34(4):85-90.

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心