特高压换流站阀厅悬吊阀地震作用研究
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
利用STAADPRO有限元软件,用反应谱法分析悬吊换流及阀阀厅在地震作用下结构反应。分析表明,在抗震设防烈度小于8度时,悬吊阀体地震作用对主体结构产生的地震力很小,设计时可不考虑;在抗震设防烈度为7度时,若地震加速度为0.15g,则阀体的最大水平位移为213.5mm,相对悬挂点的位移系数为1/70。
The seismic characteristics of the suspending valves and the valve hall are analyzed by using the response spectrum method with software STAADPRO. The results show that the impact from the seismic response of suspending valves to the main structure of the valve hall is very small at 8 degree seismic fortification intensity, so it can be ignored in design. In the case of 7 degree seismic fortification intensity the maximum horizontal displacement of the suspending valves due to seismic response could be 213.5 mm if the acceleration of ground is upto 0.15g, and thus relative displacent coefficient of the suspending point is 1/70.
引文
[1]孟繁飞,高政国,廖翌棋.大型火电厂煤斗悬吊结构抗震反应谱分析.工业建筑[J].2006,36(增):207~209,198.MENG Fan-fei,GAO Zheng-guo,LIAO Yi-qi.Response Spectrum Analysis on Earthquake-Resistant Behavior of Suspending Coal Hoppers for a Large-Scale Thermal Power Plant[J].Industrial Construction.2006,36(S):207~209,198.
    [2]GB/J50011—2001,建筑抗震设计规范[S].
    [3]IEC62271-2,High-voltage Switchgear and Controlgear-Part2:Seismic Qualification for Rated Voltages of72.5kV and Above[S].

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心