特殊土壤情况下HVDC输电线路单极模式运行时的地表电位计算
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
高压直流输电线路(HVDC)单极经大地回路运行产生的地表电位分布对交流输电系统有负面影响。实际情况下的土壤结构是非常复杂的。本文阐述运用目前国内外接地计算较多采用的CDEGS软件包中的MALZ模块对复杂土壤模型进行计算,分析湖泊、大型金属管道等对电位分布的影响,以总结其对地表电位分布的影响规律。
The ground surface potential,arisen from the single-pole ground-retum mode operation of HVDC transmission line,may have negative effects on AC power systems.The real soil structure is very complicated,This paper illustrates the application of worldwide popular software CDEGS in various soil structures,and case studies are carried out by employ- ing it.Influence factors such as the grounding electrodes and soil structures etc.are also discussed to summarize the characteristics of the ground surface potential distribution.
引文
[1]谢广润.电力系统接地技术.第1版.北京:中国电力出版社,1991,1
    [2]谢广润.高压静电场.第2版.上海:上海科学技术出版社,1987,5
    [3]藤吉文.固体地球物理学概论.第1版.北京:地震出版社,2003.2
    [4]F.Dawalibi,N.Barbeito.Measurements and Computations of the Performance of Grounding Systems Buried in Mul- tilayer soils.IEEE Transaction on Power Delivery,Vol.6,No. 4,October 1991.1483~1488
    [5]W.Ruan,J.Ma,J.liu,F.P.Dawalibi.Performance of HVDC Ground Electrode in Various Soil Structures.Power System Technology,2002.Proceedings.PowerCon 2002.Interna- tional Conference(Volume 2),13~17 Oct.2002,962~968