Improved Control Strategy Based on Splitting-Capacitor for Grid-Connected Inverter
详细信息    查看官网全文
摘要
As a single current feedback method,the WAC(Weighted-Average Control) strategy achieves low distortion of the current with less steady-state error,and it also avoids the capacitance design problems that exist in traditional method based on splitting-capacitor.But the WAC strategy is limited to the interference from grid and an neglected resonant frequency.In this paper,an active damping method is used to improve the grid-connected current quality and restrain the resonance of system while degrading the control system.In addition,a grid voltage feed-forward control strategy is proposed to resist the grid disturbance which can not only change the control transfer function,but also have a negative effect on active damping method.Effectiveness and feasibility of the proposed strategy are verified by the simulation results.
As a single current feedback method,the WAC(Weighted-Average Control) strategy achieves low distortion of the current with less steady-state error,and it also avoids the capacitance design problems that exist in traditional method based on splitting-capacitor.But the WAC strategy is limited to the interference from grid and an neglected resonant frequency.In this paper,an active damping method is used to improve the grid-connected current quality and restrain the resonance of system while degrading the control system.In addition,a grid voltage feed-forward control strategy is proposed to resist the grid disturbance which can not only change the control transfer function,but also have a negative effect on active damping method.Effectiveness and feasibility of the proposed strategy are verified by the simulation results.
引文
[1]Frede Blaabjerg,Remus Teodorescu,Marco Liserre,et.al.,Overview of control and grid synchronization for distributed power generation systems,IEEE Trans,on Industry Electronics,53(5):1398-1409,2006.
    [2]Xiao Huafeng,Xie Shaojun,Chen Yang,et.al.,An optimized transformerless photovoltaic grid-connected inverter,IEEE Trans,on Industry Electronics,58(5):1887-1895,2011.
    [3]Zeng Zheng,Zhao Rongxiang,Tang Shengqing,et.al.,An Overview on advanced grid-connected inverters used for decentralized renewable energy resources,Proceeding of the CSEE,33(24):1-12,2013.
    [4]S.Ahn,J.Park,I.Chung,et.al.,Power-sharing method of multiple distributed generators considering control modes and configurations of a micro-grid,IEEE Trans,on Power Delivery,25(3):2007-2016,2010.
    [5]J.Ma,C.Mi,S.X.Zheng,T.Wnag,et.al.,Application of voltage harmonic distortion positive feedback for islanding detection,Electric Power Components and System,41(6):641-652,2013.
    [6]C.N.M.Ho,V.S.P.Cheung,H.S.H.Chung,Constant frequency hysteresis current control of grid-connected VSI without bandwidth control,IEEE Trans,on Power Electronics,24(11):pp.2484-2495,2009.
    [7]Kamarn Jalili,Steffen Bernet,Design of LCL filters of active-front-end two-level voltage-source converters,IEEE Trans,on Industry Electronics,56(5):1674-1689,2009.
    [8]M.Lindgren,J.Svensson,Control of a voltage-source converter connected to the grid through an LCL-filter-application to active filtering,IEEE PESC'98,Fukuoda,1998.
    [9]Wang Yaoqiang,Wu Fengjiang,Sun Li,et.al.,Control strategy for grid-connected inverter with an LCL output filter,Proceedings of the CSEE,31(12):34-39,2011.
    [10]Wu Xiaojie,Sun Wei,Dai Peng,et.al.,An active damping method of virtual resistor in parallel with capacitor,Trans,of China Electrotechnical Society,25(10):122-128,2010.
    [11]E.Twining,D.G.Holmes,Grid current regulation of a three-phase voltage Source inverter with an LCL input filter,IEEE Trans,on Power Electronics,18(3):888-895,2003.
    [12]Shen Guoqiao,Xu Dehong,Current control for grid-connected inverters by splitting the capacitor of LCL filter,Proceedings of the CSEE,28(18):36-41,2008.
    [13]Guoqiao Shen,Xuancai Zhu,Jun Zhang,et.al.,A new feedback method for PR current of LCL-filter-based grid-connected inverter,IEEE Trans,on Industrial Electronics,57(6):2333-2041,2010.
    [14]Zhuang Chao,Ye Yongqiang,Zhao Qiangsong,et.al.,Analysis and improvement of the control strategy of LCL grid-connected inverter based on split-capacitor,Trans,of China Electrotechincal Society,30(16):85-93,2015.
    [15]Yin Jinjun,Duan Shanxu,Liu Bangyin,Stability analysis of grid-connected inverter with LCL filter adopting a digital single-loop controller with inherent damping characteristic,IEEE Trans,on Industrial Electronics,56(2):380-388,2009.