铁路站房高大空间渗风量与温度梯度测试研究
详细信息    查看全文 | 推荐本文 |
  • 英文篇名:Test on Infiltration Air Volume and Temperature Gradient of the Large Space for Railway Station
  • 作者:赵金罡 ; 于靖华 ; 杨清晨 ; 田利伟 ; 郭辉 ; 陶俊威 ; 彭珊
  • 英文作者:ZHAO Jing-gang;YU Jing-hua;YANG Qing-chen;TIAN Li-wei;GUO Hui;TAO Jun-wei;PENG Shan;School of Environmental Science and Engineering, Huazhong University of Science and Technology;College of Architecture, China Railway Siyuan Survey and Design Group Limited Company;
  • 关键词:高大空间 ; 分层空调 ; 热负荷 ; 温度梯度 ; 测试
  • 英文关键词:large space;;stratified air conditioning;;heating load;;temperature gradient;;test
  • 中文刊名:JZRK
  • 英文刊名:Building Energy & Environment
  • 机构:华中科技大学环境科学与工程学院;中铁第四勘察设计院集团有限公司建筑院;
  • 出版日期:2019-06-25
  • 出版单位:建筑热能通风空调
  • 年:2019
  • 期:v.38;No.208
  • 语种:中文;
  • 页:JZRK201906004
  • 页数:5
  • CN:06
  • ISSN:42-1439/TV
  • 分类号:19-22+34
摘要
针对夏热冬冷地区铁路旅客站房冬季渗透风及热分层问题,以武汉某铁路站房为调研对象,对候车区高大空间开口尺寸,渗透风量和温度分布进行实地调研。结果表明,调研时段站房总渗透风量达到61.2万m~3/h,折合换气次数为2.1次/h,其中高架候车室渗透风量为54.7万m~3/h,折合换气次数为2.0次/h,整个站房单位空调面积渗透风热负荷为68.5 W/m~2。高大空间下部候车区温度为15.0℃,顶部温度为20.0℃,上下温差为5℃,温度梯度下部较高,上部平缓,平均约为0.28℃/m。调研结果为站房运行节能提供了技术参考。
        Aiming at the problem of air infiltration and heat stratification in the railway passenger station in the hot-summer and cold-winter region, a railway station in Wuhan is taken as the research object, and the on-site investigation about the opening size, infiltration air volume and temperature distribution of the waiting hall large space is conducted. The results indicate that during the survey period, the total infiltration air volume of the station reaches612000 m3/h, which is equivalent to air change rate of 2.1 times per hour. And the infiltration air volume of elevated waiting hall is 547000 m~3/h, which is equivalent to air change rate of 2.0 times per hour. The infiltration air heating load of per unit air-conditioning area of the whole station is 68.5 W/m~2. The temperature of the lower part of the large space is 15.0 ℃,while that of the upper part is 20.0 ℃, and the temperature difference between the upper and the lower parts is 5℃.The temperature gradient of the lower part is higher, while the upper is gentle, and the average is about 0.28 ℃/m. The results of the investigation provide technical reference for the energy saving operation of the station.
引文
[1]张玲玲,刘紫辰,辛玉富,等.高大空间空调系统节能设计[J].暖通空调, 2013(S1):234-237
    [2]郑文国.深圳北站空调通风系统设计[J].暖通空调,2010,40(3):50-53
    [3]蔡珊瑜.福州南站分层空调数值模拟分析与负荷节能率优化[J].发电与空调, 2014, 35(2):68-73
    [4]贾学斌,张雷,陈敬文.高铁站房大空间空调送风的气流组织分析与研究[J].铁道科学与工程学报, 2015, 12(4):762-768
    [5]喻李葵,余雷模,马卫武,等.铁路客运站候车厅冬季供暖系统优化分析[J].中南大学学报(自然科学版), 2015, 48(5):1900-1908
    [6]何列波,喻李葵,王晓宗,等.候车厅冬季分层空调CFD模拟研究与实验验证[J].建筑热能通风空调, 2012,(3):56-59
    [7]辛峰,杨燕慧,杨德福.高大空间分层供暖室内气流的数值模拟研究[J].建筑节能, 2009,(4):21-23.
    [8]杨德福.大空间分层空调对流热转移数值模拟研究[D].成都:西南交通大学, 2007.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700